3 hours ago: How to recoil the starter spring - Champion R484TR?

Mend Vokera Home Heating Systems

Mend Heating, Home Heating Systems
Find out how to mend it for free.

Ask Question
Mend Heating, Home Heating Systems
Free repair help for Vokera home heating systems

Mend > Home Heating Systems

Mend Heating, Home Heating Systems

Vokera boiler losing ptressure?

I have installed in the loft of our bungalow a vokera linea series combi-boiler, (domestic & heating
In the owners manual it advises that we keep the pressure between 1 to 2 psi, it achieves this when it is functioning,ie heating is operating or running the bath etc.
When the unit is at idle the pressure gauge needle comes to rest on the dial needle stop ie below zero, I then repressurise to 1.5 psi, after a few days depending on usage I need to top it up again, is this normal, if I did not repressurise, would the boiler run dry and eventually blow up

Mr. K. Shears
November 2010
sounds like you need your expansion vessel re-pressurised and the pressure relief valve replaced.

Ian
November 2010
Its normal for a this particular boiler, cut your losses now and fit something of a reputable make!

boiler bill
November 2010

Automatic Answer

We may have found other answers which could help you.

Click here for Boiler Losing Installed

Mend Heating, Home Heating Systems
Free repair help for Vokera home heating systems

Other models...

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Free repair help for Vokera home heating systems