2 hours ago: BT Studio 4500 cordless telephone?

Mend Home Heating Systems

Mend Heating, Home Heating Systems
Find out how to mend it for free.

Ask Question
Mend Heating, Home Heating Systems
Mend repair fix home heating systems

Mend > Home Heating Systems

Mend Heating, Home Heating Systems

Increase pressure in Ideal C95FF combi boiler?

We recently disconnected a radiotor before decorating, but once it was reconnected and the valves opened again the pressure indicator on the boiler dropped to 0 psi and now there is no heating operational. Hot water works fine. How do you add pressure to the heating system with this boiler?

Gareth
September 2008
from TOTAL BUILD AND HEATING do you have A filling loop on boiler if so just open and fill to 1.5 bar plus make sure all rads i.e vants are open to let air out 1 at a time plus keep toping up boiler when doing this untill you have 1.5 bar MINT HAY

JUSTTO GOOD ANDY 20 EXP
September 2008

Automatic Answer

We may have found other answers which could help you.

Click here for Boiler Disconnected Reconnected

Mend Heating, Home Heating Systems
Mend repair fix home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Mend repair fix home heating systems