Sounds as though you are getting insufficient water  flow  across the  exchanger. Try increasing the flow  rate via  the  cold water supply tap located underneath the boiler. The other thing could be that the  flow  regulator valve situated on the DHW supply  pipe  right at the exchanger is swollen and reducing  your water rate  through the exchanger.
                 Bill
                
 May 2009