The boiler overflow pipe that goes outside is dripping hot water frequently. The pressure is also very high at times. The water & heating are approx. half way up for heat setting, so not very high.
Please could anyone answer - Why is the pressure high & how can i stop the water leaking out? it has been happening for sometime as the lower wall is greeny /mossy/ damp where the warm falls.
you need to have the expansion vessel re-pressurised and the pressure relief valve replaced. best to clean out the flexible expansion hose at the same time as they are very liable to blocking up on this boiler.