Recent: Toyota overlocker model 3400 D?

Mend Vokera Home Heating Systems

Mend Heating, Home Heating Systems
Find out how to mend it for free.

Ask Question
Mend Heating, Home Heating Systems
Free repair help for Vokera home heating systems

Mend > Home Heating Systems

Mend Heating, Home Heating Systems

Vokera Linea Max - hot cycling after re pressurising expansion vessel?

I have re pressurised the expansion vessel to 12psi having isolated and drained the boiler. The vessel now holds it's pressure, valve is dry and no signs of water from prv / external drain pipe. No error code on boiler.
Boiler pressure restored to 1bar cold, water clean.
On start up. the boiler will heat correctly to lower temperatures, both HW & CH (60 Deg os so).
However, when the temperature is set to Max, the stystem will heat to around 85 Deg but the boiler then cycles hot - the boiler coming on every 20-30 seconds and running for about the same? Boiler pressure will increase to around 2 bar.
Any ideas much appreciated.

maccag
September 2010

Automatic Answer

We may have found other answers which could help you.

Click here for Hot After Expansion Vessel

Mend Heating, Home Heating Systems
Free repair help for Vokera home heating systems

Other models...

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Free repair help for Vokera home heating systems