Built into the boiler is an oblong expansion vessel,there is an air valve that should be accessible,open pressure relief valve to drop the pressure in the central heating system,then check the air pressure in the expansion vessel    
as you would a car tyre then if needed pump up to 1.0 bar                                                                                                                                                                 If pressure starts to increase again when its running the expansion vessel could need replacing
                