Recent: How to remove roller from lawnmower?

Mend Home Heating Systems

Mend Heating, Home Heating Systems
Find out how to mend it for free.

Ask Question
Mend Heating, Home Heating Systems
Click here to mend home heating systems

Mend > Home Heating Systems

Mend Heating, Home Heating Systems

prisma combi?

i put a question in recently asking do i drain the system until i have no pressure showing on the clock gauge and then pump this up through the valve at the top until i get 1 bar pressure on the clock on the boiler

P
December 2006
thanks gas aid i did drain water out until pressure clock read 0 when i tried to inflate presure it was registering on the presure clock on boiler does this mean there is still water in system what method should i use to drain boiler

PETER@norman76.fsnet.co.uk
December 2006
I presume you are talking about the expansion vessel...

You need to drain the boiler and pump the expansion vessel up to 1 Bar... You need to do this with a foot pump with it's own gauge... You do not want the boiler to register anything whilst pumping up the vessel, once at a bar... You then need to reconnect the boiler and fill the system to 1bar as shown by the boiler with water.

GasAid.co.uk
December 2006

Automatic Answer

We may have found other answers which could help you.

Click here for Pressure Showing Gauge

Mend Heating, Home Heating Systems
Click here to mend home heating systems

How to mend ...

Find out how to mend just about anything howtomendit.com for free repair help, information and advice.
Mend Heating, Home Heating Systems
Click here to mend home heating systems